Mitsubishi Electric F700 Instruction Manual page 86

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Parameter
Name
7
Acceleration time
8
Deceleration time
Acceleration/
deceleration
20
reference frequency
Acceleration/
deceleration time
21
increments
Second
acceleration/
44
deceleration time
Second
45
deceleration time
Electronic thermal
9
O/L relay
Second electronic
51
thermal O/L relay
DC injection brake
10
operation frequency
DC injection brake
11
operation time
DC injection brake
12
operation voltage
13
Starting frequency
Holding time at a
571
start
Load pattern
14
selection
Incre
Initial
Range
ments
Value
Set the motor acceleration time.
0.1/
0 to 3600/
5/15s
*4
*4
0.01s
360s
Set the motor deceleration time.
0.1/
0 to 3600/
10/30s
*5
0.01s
360s
*5
Set the frequency referenced as
acceleration/deceleration time. Set the
0.01Hz
60Hz
1 to 400Hz
frequency change time from stop to Pr. 20 for
acceleration/deceleration time.
Increments: 0.1s
0
Range: 0 to 3600s
1
0
Increments: 0.01s
1
Range: 0 to 360s
0.1/
0 to 3600/
Set the acceleration/deceleration time
5s
0.01s
360s
when the RT signal is on.
0 to 3600/
Set the deceleration time when the RT signal
0.1/
360s
is on.
9999
0.01s
9999
Acceleration time = deceleration time
Rated
0 to 500/
Set the rated motor current.
0.01/
inverter
0 to 3600A
*6
0.1A
*6
current
*6
Valid when the RT signal is on.
0 to 500A/
Set the rated motor current.
0.01/
0 to 3600A
9999
*7
0.1A
*7
*7
9999
Second electronic thermal O/L relay invalid
Set the operation frequency of the DC
0 to 120Hz
injection brake.
0.01Hz
3Hz
Operate when the output frequency
9999
becomes less than or equal to
Pr.13 Starting frequency.
0
DC injection brake disabled
0.1s
0.5s
Set the operation time of the DC injection
0.1 to 10s
brake.
0
DC injection brake disabled
Set the DC injection brake voltage (torque).
4/2/1%
0.1%
*8
0.1 to 30%
*8
0.01Hz
0.5Hz
0 to 60Hz
Starting frequency can be set.
Set the holding time of Pr.13 Starting
0.0 to 10.0s
frequency.
0.1s
9999
9999
Holding function at a start is invalid
0
For constant-torque load
1
1
1
For reduced-torque load
Description
Initial values differ according to the inverter
capacity. (7.5K or less/11K or more)
Initial values differ according to the inverter
capacity. (7.5K or less/11K or more)
Increments and
setting range of
acceleration/
deceleration time
setting can be
changed.
The setting depends on the inverter
capacity (55K or less/75k or more)
The setting depends on the inverter
capacity (55K or less/75k or more)
Initial values differ according to the
inverter capacity. (7.5K or less/11K to
55K/75K or more)
Parameter list