Mitsubishi Electric F700 Instruction Manual page 63

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Start/stop from the operation panel (PU
operation mode)
9.
Acceleration → constant speed
Perform 20mA input.
The frequency on the indication increases by
the Pr. 7 Acceleration time and "
(60.00Hz) appears.
10.
Deceleration
Input 4mA or less.
The frequency on the indication decreases
by the Pr. 8 Deceleration time, and the motor
stops rotating with "
on the indication.
[FWD] indication or [EXT] indication flickers.
11.
Stop
Press
.
[FWD] indication or [REV] indication turns OFF.
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to the chapter 4 of
Manual (applied).)
Change the frequency (60Hz) at the maximum current input (at 20mA, initial value)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 64.)
Change the frequency (0Hz) at the minimum current input (at 4mA, initial value)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
the chapter 4 of
56
Operation
"
" (0.00Hz) displayed
the Instruction Manual (applied).)
Display
Current signal
source
(20mADC)
Current signal
source
(4mADC)
Flickering
Stop
the Instruction