Cable and Connector Requirements

You must provide your own cables to connect to a remote power source (for example, a circuit breaker
panel) in your equipment rack or office. Cables must be sized to meet the following criteria:
• rated for at least 150A service to allow for a fully loaded E1200 system at low input voltage per your
local electrical codes
• limits voltage drop across the cable length to 0.5V or less
Before you make the cable connections, apply a coat of antioxidant paste to un-plated metal contact
surfaces. File un-plated connectors, braided straps, and bus bars to a shiny finish. It is not necessary to
file and coat tinned connectors or other plated connection surfaces, such as on the E1200 PEM studs.

Installing DC PEMs

CAUTION: Provide an easily accessible external disconnect. Dell Force10 recommends that you use a 150A
circuit breaker.
CAUTION: Un interrupteur externe doit être fournis et doit être facilement accessible. Dell Force10
recommande l'utilisation d'un disjoncteur de 150Ampères. Eine leicht zugängliche Trennvorrichtung muss in
der.
CAUTION: Verdrahtung eingebaut sein. Dell Force10 empfiehlt, dass Sie einen 150A Sicherungsautomaten
benutzen.
Each E1200 system requires at least one load-sharing DC PEM to operate. Two units are recommended
for full facility redundancy.
Parameter
Maximum DC PEM Input Current
Maximum Power Dissipation
36
|
Installing DC Power Supplies
Latch Release
Status
-48/-60Vdc
150A, 7200VA
CC-E1200-PWR-DC
Over-current protector
Specifications
150A
6850W (21,598 BTU/hour)