11. Action explanation

11.1 OUT1 PID, PI, PD, P actions

PI action : When derivative time is set to "0"
PD action : When integral time is set to "0"
P action : When both integral and derivative time are set to "0"
[8] Integral time and [9] Derivative time can be set in the Sub setting mode. (p.14)
[48] Direct (Cooling)/Reverse (Heating) action can be selected in the Setup mode. (p.21)
ON
Control
action
OFF
Relay contact
output
Cycle action is performed according to deviation
+
Non-contact
voltage output
Cycle action is performed according to deviation
+
DC current
output
Changes continuously according to deviation
Indicator
(OUT1) Green
part : Acts ON or OFF.

11.2 OUT1 ON/OFF action

ON/OFF action: When OUT1 proportional band is set to "0" or "0.0"
[6] OUT1 proportional band can be set in the Sub setting mode. (p.14)
[48] Direct (Cooling)/Reverse (Heating) action can be selected in the Setup mode. (p.21)
ON
Control
action
OFF
Relay contact
output
+
Non-contact
voltage output
+
DC current
output
Indicator
(OUT1)Green
part: Acts ON or OFF.
Reverse (Heating) action
Proportional band
SV setting
7
7
7
8
8
8
7
+
7
+
12V DC
12/0V DC
8
8
+
+
7
7
20mA DC
20 to 4mA DC
8
8
Lit
Reverse (Heating) action
Hysteresis
SV setting
7
8
+
7
12V DC
8
+
7
20mA DC
8
Lit
Direct (Cooling) action
Proportional band
SV setting
7
8
Cycle action is performed according to deviation
+
+
7
7
0V DC
0V DC
8
8
Cycle action is performed according to deviation
+
+
7
7
4mA DC
4 to 20mA DC
4mA DC
8
8
Changes continuously according to deviation
Unlit
Unlit
Direct (Cooling) action
SV setting
7
7
8
8
7
+
7
0V DC
0V DC
8
8
7
7
+
4mA DC
4mA DC
8
8
Unlit
Unlit
29
ON
OFF
7
7
8
8
+
7
7
0/12V DC
12V DC
8
8
+
7
7
20mA DC
8
8
Lit
Hysteresis
ON
OFF
7
8
+
7
12V DC
8
+
7
20mA DC
8
Lit

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt4b

Table of Contents