Panasonic KT4H User Manual page 55

Table of Contents

Advertisement

Modbus
function code
03H/06H
0050H
03H/06H
0051H
03H/06H
0052H
03H/06H
0053H
06H
0070H
03H
0080H
03H
0081H
03H
0082H
03H
0083H
03H
0085H
03H
0086H
03H
0087H
Data item
Backlight
PV color
PV color range
Backlight time
Key operation change flag clearing
PV (Process variable)
OUT1 MV
OUT2 MV
SV (When SV rises or falls)
Status flag
0000 0000 0000 0000
CT1 current value
CT2 current value
55
0000H: All are backlit
0001H: Only PV display is backlit
0002H: Only SV display is backlit
0003H: Only action indicators are backlit
0004H: PV+SV displays are backlit
0005H: PV+ action indicators are backlit
0006H: SV+ action indicators are backlit
0000H: Green
0001H: Red
0002H: Orange
0003H: When Alarm ON, Green
0004H: When Alarm ON, Orange
0005H: PV color changes continuously
0006H: PV color changes continuously
+ Alarm ON: Red
Set value, Decimal point ignored
Set value
0000H: No action
0001H: All clearing
Decimal point ignored
Decimal point ignored
Decimal point ignored
Decimal point ignored
0
2
: OUT1
(DC current output type: Not fixed)
1
2
: OUT2
2
2
: Alarm 1 output
3
2
: Alarm 2 output
4
2
: Not used, always 0
5
2
: Not used, always 0
6
2
: Heater burnout alarm output 0: OFF, 1: ON
(When Sensor burnout, 0: OFF)
7
2
: Not used, always 0
8
2
: Overscale
9
2
: Underscale
10
2
: Control output OUT/OFF
0: ON, 1: OFF
11
2
: During Auto-tuning/Auto-reset
0: OFF
1: During Auto-tuning/Auto-reset
12
2
: OUT/OFF key function
0: OUT/OFF function, 1: Auto/Manual control
13
2
: Not used, always 0
14
2
: Auto/Manual control
0: Automatic control, 1: Manual control
15
2
: Change in key operation
0: No, 1: Yes
Decimal point ignored
Decimal point ignored
Data
Red
Red
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON
0: OFF, 1: ON

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt4b