Reference conditions
Input current I
E
Input voltage U
E
Frequency f
E
Waveform
Load resistor R
B
Ambient temperature T
Auxiliary voltage U
Warm-up time
External fields / external
interference
Influence effects of the
input measuring voltage
from U
to 1.2U
EN
input measuring current
from I
to 1.2 I
EN
EN
the auxiliary voltage
0.8 to 1.2 U
at DC
HN
0.9 to 1.1 U
at AC
HN
ambient temperature
frequency (45-65 Hz)
harmonics
(to the 32nd harmonic)
load resistor
warm-up
E50417-K109U-C322-A
I
EN
U
f
EN
sinusoid, harmonic distortion ≤ 5 %
R
23 °C ± 1°C
U
U
H
≥ 15 min
none
related to A
(other signals at reference conditions)
≤ 0.2 %
EN
≤ 0.2 %
≤ 0.1 %
≤ 0.1 %
≤ 0.2 % / 10 K
≤ 0.03 % / Hz
≤ 0.02 % every 10 % harmonic
distortion
≤ 0.1 % for load changes from 0Ω to
15V/I
≤ 0.3 %
1
± 1 %
± 1 %
EN
± 1 %
± 1 %
BN
HN
N
AN
SIMEAS
15