Assumptions:
Mounting of the transducers on supporting rail without spacing,
output load caused rated burden (R
output 1 = 10 mA
output 2 = 10 mA
output 3 = 10 mA
Measuring voltage: U
Procedure:
A power loss of 2.25 W in the transducer is derived
from diagram 2.
An additional power loss of approx. 100 mW in the
voltage path is derived from diagram 2.
The result is a total power loss in the transducer of 2.35
W.
A permanently admissible ambient temperature about
55° is derived from diagram 1.
36
BIN
}
= 3 ∗ 100 V.
L-L
SIMEAS
= 375 Ω).
Σ I
= 30 mA
A
E50417-K109U-C322-A1