Siemens 7KG6000-8AA Operating Instructions Manual page 16

Universal transducer
Table of Contents

Advertisement

Other technical specifications
Insulation tests,
type tests
Inputs (currents against currents
and voltages)
Inputs against all analog outputs,
interface, pulse output, and
auxiliary voltage
Auxiliary voltage against all analog
outputs, interface and pulse output
Insulation tests,
routine tests
Inputs (currents against currents
and voltages)
Inputs against all analog outputs,
interface, pulse output, and
auxiliary voltage
Auxiliary voltage against all analog
outputs, interface and pulse output
Analog outputs, interface and pulse
output mutually
Caution!
Analog output 1 is electrically connected to the interface
16
according to IEC 61010-1
3.7 kV; 50 Hz; sinusoid;
6.8 kV surge voltage;
1.2/50 µs; R
5.55 kV; 50 Hz; sinusoid;
10.2 kV surge voltage;
1.2/50 µs; R
3.7 kV; 50 Hz; sinusoid;
6.8 kV surge voltage;
1.2/50 µs; R
according to IEC 61010-1
2.2 kV; 50 Hz; sinusoid
3.25 kV; 50 Hz; sinusoid
2.2 kV; 50 Hz; sinusoid
700 V DC
SIMEAS
= 500 Ω
i
= 500 Ω
i
= 500 Ω
i
E50417-K109U-C322-A1