1.17 Configuration

With the cable 7KG6051-8BA, the transducer is connected to a
PC running "SIMEAS PAR". How to start the program is
described in the SIMEAS PAR manual. The program guides the
user through the required procedures. The changes are saved in
the transducer.
The interface cable must be connected correctly (diagram). The
interface must not be short-circuited for a longer period.
PC-cable
colour
RS 232C (V.24)
green
white
brown
Transducer with RS 485-interface:
To calibrate and configure the device, it must be disconnected
from the Bus and connected to the PC. Through the
communication with the PC it is switched over to the parameter
mode. If the VDEW mode has been configured, this will only be
activated after the configuration has been finished and a short
interruption of the auxiliary voltage has been effected. Each of the
open ends (between terminal "a" and "b") of the Bus must be
terminated with an Resistor of 220 Ω Ω Ω Ω .
32
transducer
TXD
RXD
GND
SIMEAS
RS 485
b
a
GND
E50417-K109U-C322-A1
terminal
11
12
13