Table 4- 4
X101, terminal block for routing the auxiliary voltage connecting cables
Terminal
1
2
3
4
5
6
The maximum load-carrying capacity of the auxiliary power supply system is 80 A according to IEC (or 80 A according to
UL).
Conductor cross section: single-wire and flexible cables 0.5 to 35 mm
Tightening torque: 2 Nm
Auxiliary power module in the Line Connection Module
The auxiliary power module in the Line Connection Module consists of the -X100 terminal
block for feeding in and routing the auxiliary voltages in both directions. No voltage taps are
available to the customer.
Table 4- 5
X100, terminal block in the Line Connection Module for routing the auxiliary voltages
Terminal
1
1
2
2
3
3
4
4
5
5
6
6
-F24
The maximum load-carrying capacity of the auxiliary power supply system is 80 A according to IEC (or 80 A according to
UL).
Conductor cross section: single-wire and flexible cables 2.5 to 16 mm
Tightening torque: 2 Nm
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
Designation
Assigned voltages
L1
Line voltage (for fan supply via transformer):
380 to 480 V 2 AC or
L2
500 to 690 V 2 AC (max. 759 V AC)
L1
230 V 1 AC (max. 265 V AC)
N
P24
24 V DC for the electronics power supply (max. 30
V DC)
M
Voltage tap
Line voltage:
380 to 480 V 2 AC or
500 to 690 V 2 AC (max. 759 V AC)
230 V 1 AC (max. 265 V AC)
24 V DC for the electronics power supply (max. 30 V DC)
24 V DC fuse
2
2
Electrical installation
4.4 Connections
Rated current
Max. 80 A
Max. 80 A
Max. 80 A
Rated current
Max. 80 A
Max. 80 A
Max. 80 A
Max. 10 A