ABB COM600 series User Manual page 31

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756125
COM600 series, version 4.1
User's Manual
Description
Degree of protection by
enclosure
Clearance and creepage dis-
tances
Table 4.1-8 Power supply and module tests
Description
Auxiliary voltage
Aux. voltage interruptions
Ripple in auxiliary DC voltage
Power consumption
Table 4.1-9 Insulation tests
Description
Dielectric test
Impulse voltage test
Insulation resistance
Protective bonding impedance
The EMC immunity test level meets the requirements listed below:
Table 4.1-10 Electromagnetic compatibility tests
Description
1 MHz and 100 kHz burst dis-
turbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency field immunity
Fast transient
Power supply
RJ-45 port
Surge immunity
Power supply
Standard
According to IEC 60529
According to IEC 60255-5
Standard
According to IEC 60255-1
According to IEC 60255-11
According to IEC 60255-11 15%, f = 2 x fn
According to CE EN 61010
Standard
According to IEC 60255-5 2 kV, 50 Hz for 1 minute
According to IEC 60255-5 5 kV, 1.2/50 μs, 0.5 J
According to IEC 60255-5 >100 MΩ, 500 Vdc
According to IEC 60255-27 <0.1 Ω.
Standard
According to IEC 61000-4-18 and IEC 60255-22-1
2.5 kV
1.0 kV
According to IEC 61000-4-2, IEC 60255-22-2
6 kV
8 kV
According to IEC 61000-4-3 and IEC 60255-22-3
10 V/m (80% amp.mod.)
f=80...2700 MHz
10 V/m (pulse mod.) f=900 MHz
According to IEC 61000-4-4 and IEC 60255-22-4
2 kV
1 kV
According to IEC 61000-4-5 and IEC 60255-22-5
2 kV line-to-earth, 1 kV line-to-line
31

Hide quick links:

Advertisement

Table of Contents
loading