44
COM600 series, version 4.1
User's Manual
the IP addresses of the computers into the same subnetwork. By default, the commu-
nication from SAB600 to the COM600 computer will use TCP port 8080. Make
sure that the port is opened in the firewall of the SAB600 computer. For callbacks
from COM600 computer another port is required. This is used by the spontaneous
updates in the online diagnostic tools. By default, the software reserves a free port
for the callbacks automatically.
2. Connect either a crossover LAN cable between the computers or connect both
computers to a network switch. Use the LAN port used for local use in COM600
computer.
3. Create a project and add the Gateway object to the communication structure.
4. Type the IP address of the COM600 computer LAN port used for configuration to
the IP address property of the Gateway object.
5. Right-click the Gateway object and select Management. Verify that the communic-
ation with the COM600 computer is working properly. The first time you open the
management tool, you are required to change the COM600 user password. Click
Change password to change the password in the COM600 computer.
The COM600 user password must always be changed as
described above to ensure that the password is changed cor-
rectly for each component in the COM600 computer.
If you lose the password, you cannot access the COM600
computer either locally or remotely.
Setting the remoting communication parameters
To change the port number used for the communication from SAB600 to the COM600
computer:
1. Modify the Port Number property of the Gateway object in the SAB600 project.
2. In COM600 computer, select Start -> All Programs -> ABB -> SetRemotingPara-
meters.
3. Set the port number in Set Remoting Parameters utility.
4. Click Apply.
If multiple network adapters are used in COM600, you must specify the one used for
the SAB600 communication. In the Set Remoting Parameters utility, select the IP address
of the COM600 network adapter used for the SAB600 communication.
To change the port number used for the callbacks from COM600:
1. Close the SAB600 program.
2. In SAB600 computer, select Start -> Programs -> ABB -> Station Automation
Builder 600 -> Set Remoting Parameters.
3. Set the port number in the Set Remoting Parameters utility.
4. Click Apply.
5. Restart the SAB600 program.
1MRS756125