ABB COM600 series User Manual page 33

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756125
COM600 series, version 4.1
User's Manual
Description
Storage test
Table 4.1-13 Mechanical tests
Description
Vibration tests
Vibration response test
Vibration endurance test
Shock and bump tests
Shock response test
Shock withstand test
Bump test
Seismic test
biaxial multi-frequency
random seismic test
Table 4.1-14 EMC compliance
Complies with the EMC direct-
ive 2004/108/EC
Standards
Table 4.1-15 Product safety
Complies with the LV directive
2006/95/EC
Standards
Standard
According to IEC 60068-2-48
Test values:
72 h at +70ºC
72 h at -40ºC
Standard
According to IEC 60068-2-6 and IEC 60255-21-1
f = 10...150 Hz, ± 0.035 mm, 10...58 Hz, 5 m/s2 58...150
Hz
f = 10...150 Hz, ± 0.075 mm, 10...58 Hz, 10 m/s2 58...150
Hz
According to IEC 60068-2-27 , IEC 60068-2-29 and IEC 60255-
21-2
peak acceleration = 5 x gn, pulse duration = 11 ms, numbers
of pulses in each diretion = 3
peak acceleration = 15 x gn, pulse duration = 11 ms, number
of pulses in each direction = 3
peak acceleration = 10 x gn, pulse duration = 16 ms, number
of pulses in each direction = 1000
According to IEC 60255-21-3 test method B
2 x gn in horizontal direction, 1 x gn in vertical direction
EN 50263 (1999),
EN 60255-26 (2008),
EN 61000-6-2 (2005),
EN 61000-6-4 (2007)
EN 60255-27 (2005),
EN 60255-1 (2009)
UL recognized component for USA and Canada, UL-file number
E 231775 (High voltage power supply variant)