Power Cable Connection Diagram

1)
(PE)
PE
(PE)
1), 2)
If shielded cable is used (not required but
recommended), use a separate PE cable (1) or a cable
with a grounding conductor (2) if the conductivity of the
input cable shield is < 50% of the conductivity of the
phase conductor.
Ground the other end of the input cable shield or PE
conductor at the distribution board.
360 degrees grounding recommended if shielded cable
360 degrees grounding required
Use a separate grounding cable if the conductivity of
the cable shield is < 50% of the conductivity of the
phase conductor and there is no symmetrically
constructed grounding conductor in the cable (see
"Planning the Electrical Installation" / "Selecting the
Power Cables").
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor to
the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable.
Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
Electrical Installation
Drive
PE
2)
INPUT
L1
L2
L3
3)
L1
L2
L3
External brake
resistor
(optional)
OUTPUT
-
U2
R+
R
4)
U1
3
Motor
Grounding of the motor cable shield at the motor end
For minimum radio frequency interference:
ground the cable shield 360 degrees at the lead-through of the
motor terminal box
Conductive gaskets
or ground the cable by twisting the shield as follows: flattened
width > 1/5 · length.
a
V2 W2
4)
5)
V1
W1
~
360 degrees grounding
b > 1/5 · a
b