Maintenance

What this Chapter Contains

This chapter contains preventive maintenance instructions.

Safety

WARNING! Read the "Safety Instructions" on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.

Maintenance Intervals

If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Interval
Every 3 months
UL Type 12
Cleanliness check
Every year when
Capacitor reforming
stored
Every 6 years
UL Type 12 and all -0490-5 through -0610-5
Every 6 years
Drive module cooling fan change (frame size R7)
Every 6 years
Drive module cooling fan change (frame size R8)
Every 10 years
Capacitor change

Air FIlter Material

Enclosure Type
UL Type 12
3AUA0000006723 (qty 1)
Note: When installing the filter media, the white side must face the outside of the cabinet and the
Maintenance
Maintenance
Inlet (door)
colored side must face the inside of the cabinet.
For instruction, see section
Checking and Replacing the Air Filters (min)
Heatsink
Reforming
Replacing the Cabinet Fan
Replacing the Drive Module Fan (R7)
Replacing the Drive Module Fan (R8)
Capacitors
Outlet (roof)
3AUA0000006722 (qty 2)