Input Cable Fuses
The drive is equipped for branch circuit protection per NEC with standard T/L fuses
listed below. The fuses restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive. Check that the operating time
of the fuse is below 0.5 seconds. The operating time depends on the fuse type 
(T/L), supply network impedance and the cross-sectional area, material and length
of the supply cable. The fuses must be of the "non-time delay" type. See also
"Planning the Electrical Installation: Thermal Overload and Short-Circuit
Protection."
Note 1: In multi-cable installations, install only one fuse per phase (not one fuse per
conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and
specifications.
Note 4: Circuit breakers must not be used without fuses.
ACS800-PC type
Three-phase supply voltage 440 V, 460 V, or 480 V
-0170-5
-0210-5
-0270-5
-0300-5
-0320-5
-0400-5
-0440-5
-0490-5
-0550-5
-0610-5
Input
current
A
A
191
250
243
300
299
500
336
500
424
500
498
600
543
800
590
800
669
800
702
800
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
83
Type
UL class
JJS-400
T
JJS-400
T
JJS-400
T
JJS-400
T
JJS-600
T
JJS-600
T
JJS-800
T
JJS-800
T
JJS-800
T
JJS-800
T
PDM code: 00096931-G