Climatic ambient conditions
The following table shows the permissible climatic ambient conditions for the S7-1500
automation system/ET 200MP distributed I/O system:
Table 15- 9
Climatic ambient conditions
Am bient conditions
Temperature:
horizontal mounting posi-
tion:
vertical mounting position:
Temperature variation
Relative humidity
Barometric pressure
Pollutant concentration
Automation system
System Manual, 09/2016, A5E03461182-AD
Pe rmissible range
0 °C to 60 °C
0 °C to 40 °C
10 K/h
from 10 % to 95 %
from 1080 hPa to 795 hPa
SO
: <0.5 ppm;
2
RH <60%, no condensation
H
S: < 0.1 ppm;
2
RH < 60 %, no condensation
ISA-S71.04 severity level G1; G2; G3
15.5 Mechanical and climatic ambient conditions
C omments
To increase the service life of the display, the display
switches off when the permitted operating tempera-
ture is exceeded.
Further information about the temperatures at which
the display switches off and back on again is availa-
ble in the technical specifications of the manuals of
the CPUs.
-
Without condensation, corresponds to relative hu-
midity (RH) class 2 in accordance with IEC 61131