3. Put the strain relief (cable tie) around the cable harness, and pull the strain relief for the
cable harness tight (Figure 2).
Figure 5-15
4. Insert the shield clamp from below into the shielding bracket in order to connect the cable
shielding (Figure 3).
Figure 5-16
Functions of the shield contact
The shield contact:
● Is needed to apply cable shields (e.g., for analog modules)
● Interference currents on cable shields are diverted from the shield connection to ground
via the mounting rail. The shielding connection is not required at cable entry into the
switchboard.
Reference
Additional information on wiring the inputs and outputs can be found in the manuals for the
I/O modules.
Automation system
System Manual, 09/2016, A5E03461182-AD
Wiring front connectors for I/O modules with shield connection element (2)
Wiring front connectors for I/O modules with shield connection element (3)
5.10 Front connector for the I/O modules
Wiring
95