Configuration example of the ET 200MP with fail-safe I/O modules
①
②
③
④
⑤
Figure 2-7
Hardware and s oftware requirements
Fail-safe I/O modules S7-1500/ET 200MP can be used:
● in S7-1500 with S7-1500 F-CPUs as of firmware version V1.7
● distributed in ET 200MP with S7-1500 F-CPUs as of firmware version V1.5 and all
F-CPUs that can be selected in the hardware catalog of the TIA Portal
The following interface modules are required for fail-safe I/O modules in ET 200MP :
● IM 155-5 PN ST, as of firmware version V3.0.0
● IM 155-5 PN HF, as of firmware version V3.0.0
● IM 155-5 DP ST, as of firmware version V3.0.0
To configure and program fail-safe I/O modules S7-1500/ET 200MP , you need:
● STEP 7 (TIA Portal) as of V13 SP1
● The option package STEP 7 Safety Advanced as of V13 SP1 + HSP0086
Automation system
System Manual, 09/2016, A5E03461182-AD
Interface module
I/O modules
Power supply (optional)
Fail-safe I/O modules
Mounting rail with integrated top-hat rail
Configuration example of the ET 200MP with fail-safe I/O modules
2.4 How are SIMATIC Safety F-systems configured?
System overview