Fujitsu AUYG07LVLA Design & Technical Manual page 25

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

EXAMPLE 2
Outdoor unit
Indoor unit 1
Room 1
Design conditions
Design temperature
Indoor : 23.0°C DB / 16.0°C WB
Outdoor : 30.0°C DB
Pipe length
Main piping length : L1=10m
Branch piping length : L2=10m
Operation mode: Cooling
Selection of indoor unit
A-1 Cooling heat load
A-2 Indoor unit models
A-3 Rated capacity (TC
)
in
r
A-4
i
(
)
in
r
Connecting indoor unit
A-5
capacity (Cp)
Capacity at design temperature
A-6
(TC
)
in
d
Total capacity at design
A-7
m
(
)
in
d
Calculate the Maximum capacity of outdoor unit
B-1 Outdoor unit model
B-2 Rated capacity (TC
)
out
r
B-3 Capacity change rate by temperature conditions
B-4 Capacity change rate by indoor units connecting capacity
B-5
m
n
i n
i n
B-6 Maximum capacity of outdoor unit (TC
*1: When indoor units connecting capacity is 100% or less, rated capacity is used.
Decide system capacity
C-1 System capacity
Calculate actual capacity of each indoor unit
Actual capacity of each indoor
unit
Actual capacity of all indoor units is larger than cooling heat load of each room.
(When the connecting capacity for indoor unit is 100% or less)
Main Piping length, L1=10m
Branch
Branch
box
box
Indoor unit 2
Room 2
Room 1
Room 2
kW
2.2
2.2
AS09
AS09
kW
2.64
2.64
2.64 x 2 + 3.52 x 2 = 12.3
12. / 1 .
7.
kW
2.30
2.30
kW
2.30 x 2 +3.06 x 2 = 10.7
i
n
)
out
c
Room 1
Room 2
Room 3
kW
2.30
2.30
3.06
- (02 - 06) -
Branch Piping length, L2=10m
Indoor unit 3
Indoor unit 4
Room 3
Room 4
Room 3
Room 4
Remark
2.9
2.9
AS12
AS12
3.52
3.52
Cooling
Sum of A-3
(
1
)
3.06
3.06
See 6-1.
Sum of A-6
AO G45LBT8
kW
14.0
13.9 / 14.0 = 0.993
kW
14.0 *1
0.98 x 0.942 = 0.923
kW
14.0 x 0.993 x 0.923 = 12.8
kW
Room 4
Remark
3.06
(A3) x (C1) / (A4)
Remark
Cooling
See Fig.1
See 5-1.
(B-4) x (B-3) x (B-5)
Remark
Smaller one of (A-7)
10.7
and (B-6)
2. MODEL SELECTION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents