Fujitsu AUYG07LVLA Design & Technical Manual page 303

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

SETTINGS LIST
LED961
Setting Mode
CODE No.
Cooling
1
1
capacity shift
Switching
between
2
0
batch stop or
emergency stop
Operation
2
1
mode selecting
method
2
8
Forbidden
2
9
Forbidden
Energy saving
3
0
level setting
Frost protection
3
4
fan mode
Low noise
4
1
mode setting
Low noise
mode
4
2
operation level
setting
LED962
Setting Function
CODE No.
0
0
Standard
0
1
High power mode 1
0
2
High power mode 2
0
0
Batch stop
0
1
Emergency stop
Priority given to the
0
0
first co
and
Priority given to
0
1
external input of
outdoor unit
0
0
Forbidden
0
1
Forbidden
0
0
Forbidden
0
1
Forbidden
0
0
Level 1 (stop)
Level 2
0
1
(Limited at 50%)
Level 3
0
2
(Limited at 75%)
Level 4
0
3
(Limited at 100%)
0
0
On
0
1
Off
0
0
Off (Normal)
0
1
On (Low noise mode)
Level 1
0
0
(-3dB)
Level 2
0
1
(-6dB)
Level 3
0
2
(-9dB)
- (06 - 55) -
Factory
Remarks
setting
Use it when showing cooling capacity
l
shortage.
Use High power mode 2 when showing
cooling capacity shortage in High power
mode 1.
This mode selects the pattern of the stop
function to be operated by the external
input terminal (CN934).
l
atch stop
he stop o a indoor units
connected to same refrigerant system due
to input signal coming from CN934.
ergenc stop
stop is activated, the indoor unit does
not accept the operation command from
the remote controller. On the other hand,
when the emergency stop is released (no
input from CN934), the air conditioner
does not return to the original operation
until the indoor unit is operated by the
remote controller.
Select the priority setting of the operation
mode.
l
Priorit gi en to the first co
Priority is given to the operation mode
which is set first.
Priorit gi en to e terna input o outdoor
unit: Priority is given to the operation
mode which is set by the external input
terminal (CN932).
l
Setting forbidden
l
Setting forbidden
The capacity limit can be selected when
operating with the "Energy Saving Peak
Cut function."
The operation selection can be done by
external input terminal(CN933).
l
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance decreases.
This mode is the function to prevent
l
frosting of the propeller fan of outdoor unit
during heating operation.
When "Low noise mode ON" is selected,
l
the operating noise will be suppressed.
Without external input terminal: It operates
by selecting Low noise mode ON.
With external input terminal: The operation
selection can be done by external input
terminal(CN931) by selecting Low noise
mode OFF.
l
The noise level when operating in the low
noise mode can be set.
Cooling/heating performance decreases
by lowering operation noise level.
hen e ergenc
and
6. SYSTEM DESIGN