Assigning Power Modules to Electronic Modules/Motor Starters
The table below lists the power modules and electronic modules/motor starters you can
operate within the same potential group.
Note that certain combinations limit the maximum safety class which can be attained.
Table 2- 3
Assigning Power Modules to Electronic Modules/Motor Starters and Safety Class
Power Modules
For a
Description,
See ...
PM-E F pm DC24V
"Power module
PROFIsafe
PM-E F pm
DC24V
PROFIsafe"
PM-E F pp DC24V
"Power module
PROFIsafe
PM-E F pp
DC24V
PROFIsafe"
PM-D F DC24V
"Power module
PROFIsafe
PM-D F
DC24V
PROFIsafe"
Power Module
PM-E DC24V
manual
DC24V (bis
6ES7138-
4CA01-0AA0)
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Electronic Module/Motor Starter
can be used with all standard electronic
modules
Can only be used for:
F-DS1e-x, F-RS1e-x fail-safe motor
starters (F-MS)
Connection multiplier F-CM
PM-D F X1 power/expansion
module
Expansion modules Brake Control
xB1 and xB2
Can be used for the F-motor starters
indicated above: Brake Control xB3
and xB4 expansion modules
can be used with all standard and fail-
PM-E
safe electronic modules
2.2 Assigning Modules of an ET 200S
Use and achievable SIL/Category/PL
Safe shutdown of DO
modules of the ET 200S
series
Safe shutdown of motor
starters
Safe shutdown of motor
starters
Power supply to F-DI, F-DO
and F-RO modules:
up to 6ES7138-4FA03-0AB0
up to 6ES7138-4FC01-0AB0
up to 6ES7138-4FB02-0AB0
up to 6ES7138-4FR00-0AA0
Supply of F-DI modules, F-
DO modules:
6ES7138-4FA04-0AB0
6ES7138-4FB03-0AB0
Configuring
SIL2/Cat
egory
3/PLd
SIL3/Cat.
4/PLe
SIL2/Cat
egory
3/PLd
SIL2/Cat
egory
3/PLd
SIL3/Cat.
4/PLe