Voltage induced on current interruption limited to
•
•
Short-circuit protection of semiconductor outputs Yes, electronic
•
•
•
Overload protection of semiconductor outputs
•
Data for selecting an actuator for the relay outputs***
Switching capacity and service life of contacts
(voltage 24 VDC)
•
•
•
•
Contact protection (internal)
•
Wire break monitoring
Parallel connection of 2 outputs
Control of a digital input
Switching frequency
•
•
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
With lamp load
Semiconductor outputs
Relay outputs
Response threshold of short circuit
Response threshold (external M-short circuit) 5 A to 12 A
Response threshold (external P-short circuit)
Response threshold
Mechanical endurance (without load)
For resistive load
For inductive load in accordance with IEC
60947-5-1, DC13
For lamp load
Between P and M relay output
With resistive load
With inductive load in accordance with IEC
60947-5-1, DC13
7.2 PM-E F pm DC24V PROFIsafe Power Module
Technical Specifications
10 Hz symmetrical, maximum
L+ (-2x 47 V)
P1/P2 (1 V)
5 A to 12 A
25 A to 45 A
Yes
I >2.6 A to 2.8 A
Current
0 A
Current
10 A
8 A
6 A
4 A
2 A
1 A
Current
10 A
8 A
6 A
4 A
2 A
1 A
Power
100 W
Internal readback circuit
39 V suppressor diode
No
Not possible
Not possible
2 Hz, maximum
0.1 Hz, maximum
Fail-Safe Modules
Number of switching cycles (typ.)
10 million
Number of switching cycles (typ.)
0.23 million
0.3 million
0.38 million
0.5 million
1.0 million
2.0 million
Number of switching cycles (typ.)
0.1 million
0.15 million
0.2 million
0.3 million
0.5 million
1.0 million
Number of switching cycles (typ.)
0.12 million
81