Mitsubishi Electric GOT2000 Series Connection Manual page 186

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(For GT21,GS)
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Startup Time
Timeout Time
Host Address
Delay Time
32 bit Storage
6 - 20
6.2 Serial Connection
Set this item when change the transmission speed used for communication
with the connected equipment.
(Default: 19200bps)
Set this item when change the data length used for communication with the
connected equipment.
(Default: 8bit)
Specify the stop bit length for communications.
(Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be performed when a communication error
occurs.
(Default: 0time)
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication to time out.
(Default: 3sec)
Specify the host address (station No. of the PLC to which the GOT is
connected) in the network of the GOT.
(Default: 1)
Set this item to adjust the transmission timing of the communication request
from the GOT.
(Default: 0ms)
Select the steps to store two words (32-bit data).
(Default: Auto)
POINT
POINT
POINT
(1) Delay Time
When connecting to PLC CP-9200(H) and CP-9300MS, set the following.
CP-9200(H)
CP-9300MS
(2) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(3) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
Model name
port:0
port:1
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps
8bit (fixed)
1bit (fixed)
Even (fixed)
0 to 5times
3 to 30sec
1 to 30sec
1 to 31
0 to 30
(
10ms)
LH Order/ HL Order/ Auto
Delay Time
30ms or more
10ms or more
30ms or more