■2. Communication detail settings
Make the settings according to the usage environment.
(For FUJI MICREX-F)
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
Description
Set this item when change the transmission speed used for communication
with the connected equipment. (Default: 9600bps)
Set this item when change the data length used for communication with the
connected equipment.
(Default: 8bits)
Specify the stop bit length for communications. (Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be performed when a communication error
occurs. (Default: 0time)
Set the time period for a communication to time out.
(Default: 3sec)
Specify the host address (station No. of the GOT to which the PLC is
connected) in the connected network.
(Default: 0)
Set this item to adjust the transmission timing of the communication request
from the GOT. (Default: 5ms)
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
0 to 99
0 to 300ms