5.4 Control Panel Inside Temperature and Mounting Angle

When mounting the main unit to a control panel or similar, set the
display section as shown below.
• When the temperature inside the control panel is 40 to 55°C or
less, the mounting angle should be in the range 60 to 105
degrees.
Display
section
Control panel,
etc.
• The GOT will be deteriorated earlier if it is used at the mounting
angle other than the above. Therefore, the temperature inside the
control panel should be within 40°C.
*: When mounting an extension unit on the upper stage of
MELSECNET/H communication unit (GT15-J71LP23-25, GT15-
J71BR13) or CC-Link communication unit (GT15-J61BT13), the
operating ambient temperature must be reduced 5°C against the
maximum values described in general specifications.