6.5
Control Panel Inside Temperature and GOT
Installation Angle
GT27
Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
GT27
■Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be
within 40 °C.
GOT
Display
section
Control panel
or others
■Installing the GOT vertically
When the GOT is installed at a 90-degree angle, the control panel inside temperature must be within 55°C.
When the GOT is installed at any angle other than 90°, the control panel inside temperature must be within 40°C.
GOT
Display
section
Control panel
or others
6 INSTALLATION AND REMOVAL
194
6.5 Control Panel Inside Temperature and GOT Installation Angle
105°
60°
90°