Gt2507T-W - Mitsubishi Electric GOT2000 Series Hardware User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

GT2507T-W

Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
GT2507T-W
■Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 65 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be
within 50 °C.
GOT
Display
section
Control panel
or others
■Installing the GOT vertically
When the GOT is installed at a 90-degree angle, the control panel inside temperature must be within 65°C.
When the GOT is installed at any angle other than 90°, the control panel inside temperature must be within 50°C.
GOT
Display
section
Control panel
or others
6 INSTALLATION AND REMOVAL
196
6.5 Control Panel Inside Temperature and GOT Installation Angle
105°
60°
90°

Advertisement