Conforming Standards In The Low Voltage Directive - Mitsubishi Electric GOT2000 Series Hardware User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Applied
Test standard
standard
EN61131-2
IEC61000-4-11
: 2007
Instantaneous power failure and
voltage dips immunity
*1 The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT on a control panel.
This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI
ELECTRIC PLC.
*2 The length of a sound output cable must be 30 m or less.
*3 QP: Quasi-peak value, Mean: Average value
*4 This test item is conducted in the following conditions.
30 MHz to 230 MHz
QP: 40 dBμV/m (measured at 10 m)
230MHz to 1000MHz
QP: 47 dBμV/m (measured at 10 m)

Conforming standards in the Low Voltage Directive

The GOT complies with the following standards in the Low Voltage Directive.
EN61131-2: Programmable controllers - Equipment requirements and tests
EN60950-1: Information technology equipment - Safety
5 EMC DIRECTIVE AND LOW VOLTAGE DIRECTIVE
146
5.1 Overview
Test details
Test for checking normal operations at
instantaneous power failure
Standard value
• AC power type
0.5 cycle 0% (Interval 1 second to 10 seconds)
250/300 cycle 0%
10/12 cycle 40%
25/30 cycle 70%

Advertisement