Connector conversion box (GT16H-CNB-37S)

Specifications
■General specifications
Other specifications are the same as Handy GOT.
Item
Specifications
Operating ambient
0 °C to 55 °C
temperature
Storage ambient
-20°C to 60°C
temperature
Vibration resistance
When installing DIN rail
■Power supply specifications
Other specifications are the same as Handy GOT.
Item
Specifications
Input power supply voltage
24 V DC (+10% -15%)
Power consumption
13.7 W or less (570 mA/24 V DC) (When including the consumption current of Handy GOT)
Connector
2.2 W (90 mA/24 V DC) (When excluding the consumption current of Handy GOT)
conversion
box only
Inrush current
25 A or less (at max. load) 2 ms
Permissible instantaneous
Within 5 ms
power failure time
■Internal relay contact specifications
Item
Contact rating
Operation switch
10 mA/24 V DC
SW1 to SW6
(resistance load only)
Emergency stop switch
1 A/24 V DC (resistance
ES1 to ES3
load)
0.3 A/24 V DC (induction
load)
Grip switch
1 A/24 V DC (resistance
DSW1, DSW2
load)
0.3 A/24 V DC (induction
load)
Keylock switch (2-position
1 A/24 V DC (resistance
switch)
load)
KSWC, KSW1, KSW2
0.3 A/24 V DC (induction
load)
Frequency
Acceleration
5 Hz to 8.4 Hz
2
8.4 Hz to 150 Hz
4.9 m/s
Specifications
Each contact coordinates the operation switch status of Pressed (close)/Not pressed (open).
When the external cable is not connected, contacts are always open regardless of the switch status.
Each contact coordinates the emergency stop switch status of Pushed (open)/Return (close).
When the external cable is not connected, contacts are always open regardless of the emergency
stop switch status.
Each contact coordinates the grip switch status of Pressed (close)/Not pressed (open).
When the external cable is not connected, contacts are always open regardless of the grip switch
status.
Each contact coordinates the position of the keylock switch.
• When the key is on the left: KSW1 and KSWC are short-circuited.
• When the key is on the right: KSW2 and KSWC are short-circuited.
When the external cable is not connected, contacts are always open regardless of the keylock
switch.
7 OPTION AND COMMUNICATION CABLE FOR HANDY GOT
Half-amplitude
Sweep Count
1.75 mm
10 times each in X, Y and Z
directions
7.1 Connector Conversion Box
7
287