7.1

Connector Conversion Box

External connection devices such as Handy GOT and PLC CPU can be monitored.
Refer to the following for the PLC CPU that can be monitored.
The Connector Conversion Box relays the power supply input terminal and emergency stop switch of the Handy GOT.
It has the structure to mount or remove the Handy GOT while in operation.
7.1.1

Applicable Connector Conversion Box

The following Connector Conversion Box is applicable to the Handy GOT.
Product name
Connector Converon Box
7.1.2

Connector Conversion Box (GT16H-CNB-42S)

■1. Specifications
(1) General specifications
Other specifications are the same as Handy GOT.
Item
Operating ambient temperature
Storage ambient temperature
Vibration resistance
(2) Power supply specifications
Other specifications are the same as Handy GOT.
Input power supply voltage
Power consumption
Inrush current
Permissible instantaneous power failure time
(3) Internal relay contact specifications
Item
Operation switch
SW1 to SW6
Emergency stop switch
ES1A to ES3A
Grip switch
DSW1, DSW2
7 - 2
7.1 Connector Conversion Box
GOT2000 Series Handy GOT Connection Manual For GT Works3 Version1
Model
GT16H-CNB-42S
When installing DIN
rail
Item
Connector Conversion Box only
Contact rating
Each contact coordinates the operation switch status of Pressed (close)/Not pressed (open).
10mA/24VDC
When the external cable is not connected, contacts are always open regardless of the switch
(resistance load only)
status.
When the external cable is not connected, contacts are always open regardless of the
emergency stop switch status.
Causing a short circuit of the ES□B terminal which is close to the ES□A terminal by a short pin
(prepared by user) enables to set each contact in the close status even if the external cable is
not connected.
1A/24VDC(resistance load)
0.3A/24VDC(induction load)
When using the short-circuited ES□B terminal which is close to the ES□A terminal
• Contacts are normally operated in the close status.
• In the following situations, contacts are closed regardless of the status of the emergency stop
Each contact coordinates the grip switch status of Pressed (close)/Not pressed (open).
1A/24VDC(resistance load)
When the external cable is not connected, contacts are always open regardless of the grip
0.3A/24VDC(induction load)
switch status.
Packing for panel installation×1 (accessory), Flange for GT10-9PT5S×1 (accessory)
Screws for flange installation (M3×8)×2 (accessory)
Specifications
0 °C to 55 °C
-20°C to 70°C
Frequency
Acceleration
5 Hz to 8.4 Hz
8.4 Hz to 150 Hz
13.7W or less (570mA/24VDC) (When including the consumption current of Handy GOT)
2.2W (90mA/24VDC) (When excluding the consumption current of Handy GOT)
Each contact coordinates the emergency stop switch status of Pushed (open)/Return (close).
*1
9.4.7 Emergency stop switch wiring
When pushing the emergency stop switch, the contacts become open.
switch and the external cable.
When GT16H-CNB-42S is turned OFF
When GT16H-CNB-42S is not supplied with the power supply (DC24V)
Content
Half-amplitude
-
1.75 mm
4.9 m/s2
-
Specifications
24VDC (+10% -15%)
25A or less (at max. load) 2ms
Within 5ms
Specifications
Sweep Count
10 times each in X,
Y and Z directions