• Click MODBUS Master in the [Select CH No.] dialog box to open the device setting dialog box of
MODBUS Master.
• Input 3-00001 to Device.
Select [Host] for Network.
Click the [OK] button when settings are completed.
3-00001 is a fixed register to access to the rotary switch of the connector conversion box by the
MODBUS communication.
• Check that [@2 300001] is displayed at [Indirect] in the Action tab.
• Tick the check box of [Fixed] and enter 256.
In this example, since Net No. is fixed to 1, 256 is entered.
For fixed values, enter the value of 256×Net No.
Click the [OK] button when entering is completed.
• After checking that both Trigger and Action are set, click the [OK] button.
7.1 Connector Conversion Box
7
7 - 17