Operation Switch Wiring; Operation Switch Input - Mitsubishi Electric GOT2000 Series Hardware User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Operation switch wiring

The operation switch is connected to the PLC through an external cable and the connector conversion box.
Connection example
■Connector conversion box GT16H-CNB-42S
Handy GOT
SW-COM
SW1
SW2
SW3
SW4
SW5
SW6
■Connector conversion box GT11H-CNB-37S or GT16H-CNB-37S
Handy GOT
SW-COM
SW1
SW2
SW3
SW4
SW5
SW6
Pin layout
Product name
Model
Connector
GT16H-CNB-42S
Conversion Box
GT11H-CNB-37S
GT16H-CNB-37S

Operation switch input

The operation switch (SW1 to SW6) can directly connect to the PLC input and be used in the sequence program as general
input devices.
The operation switch is loaded into the PLC as the momentary switch of the a contact.
When wired to PLC X0
X0
In the case of handling the input as the b contact or the alternate switch, create the input in the sequence program.
9 HANDY GOT POWER WIRING AND SWITCH HANDLING
344
9.4 Switch Wiring
Connector
conversion box
Connector
conversion box
Terminal No.
SW-COM
Terminal
block 2
1
Terminal
block 1
12
Operation switch action
Y0
X0
PLC
Terminal
block 2
1
COM
2
X0
3
X1
4
X2
5
X3
6
X4
7
X5
PLC
Terminal
block 1
12
COM
11
X0
10
X1
9
X2
8
X3
7
X4
6
X5
SW1
SW2
Terminal
Terminal
block 2
block 2
2
3
Terminal
Terminal
block 1
block 1
11
10
ON
OFF
ON
OFF
SW3
SW4
SW5
Terminal
Terminal
Terminal
block 2
block 2
block 2
4
5
6
Terminal
Terminal
Terminal
block 1
block 1
block 1
9
8
7
SW6
Terminal
block 2
7
Terminal
block 1
6