Emi And Environmental Type Tests; Iec 61850-3 Type Tests - Siemens RUGGEDCOM RS969 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS969:
Table of Contents

Advertisement

Chapter 7
Certification
Section 7.4

EMI and Environmental Type Tests

This section contains the following information:
Section 7.4.1, "IEC 61850-3 Type Tests"
Section 7.4.2, "IEEE 1613 Type Tests"
Section 7.4.3, "IEC Environmental Type Tests"
Section 7.4.1

IEC 61850-3 Type Tests

Table: IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
38
Description
ESD
Enclosure Contact
Radiated RFI
Enclosure ports
Burst (Fast Transient)
D.C. Power ports
A.C. Power ports
Earth ground ports
Surge
D.C. Power ports
A.C. Power ports
Induced
(Conducted) RFI
D.C Power ports
A.C. Power ports
Earth ground ports
Magnetic Field
Enclosure ports
Voltage Dips
D.C. Power ports
& Interrupts
A.C. Power ports
Damped Oscillatory
D.C. Power ports
A.C. Power ports
Mains Frequency
Voltage
D.C. Power ports
Enclosure Air
Signal ports
Signal ports
+/- 4kV line-to-earth,+/- 2kV line-to-line
+/- 2kV line-to-earth,+/- 1kV line-to-line
+/- 4kV line-to-earth,+/- 2kV line-to-line
Signal ports
40 A/m continuous,1000 A/m for 1 s
30% for 0.1s, 60% for 0.1s,100% for 0.05s
30% for 1 period,60% for 50 periods
100% for 5 periods,100% for 50 periods
Signal ports
2.5kV common,1kV differential mode @ 1MHz
2.5kV common,1kV differential mode @ 1MHz
2.5kV common,1kV differential mode @ 1MHz
Signal ports
Test Levels
+/- 8kV
+/- 15kV
20 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
10V
10V
10V
10V
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
EMI and Environmental Type Tests
RUGGEDCOM RS969
Installation Guide
Severity
Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
N/A
N/A
N/A
2
N/A
3
3
3
4
4

Advertisement

Table of Contents
loading

Table of Contents