Appendix A: Technical Specifications

iBox
Power
Power Supply Input Options
Requirements
Power Consumption
Inrush Current
Power Supply Protection
Communi-
Maintenance Port
cation Ports
Standard Serial Communication
Ports (3)
UTC Time Port
(in place of one serial port)
Digital Inputs
General
Burden
Wetting Options
GE Information
Installation and Maintenance Guide
20-60 Vdc
7 Watts (maximum)
Less than 0.5A peak
Input fuse
Reverse polarity protection provided
WESMAINT DB-9-F, EIA 232 @ 9600 bps
DB-9-F, EIA 232/485 up to 38400 bps (concurrently)
Software configurable
Jumper selectable (JP3) Radio Key output on Port 1
36 Vdc max., 3 A peak max., 0.1 sec ON, 10% duty
cycle
DB-9-F, EIA 232 Port 2
Up to eight bipolar optically isolated (2000 V
From 1.9 mA to 5.5 mA
max. power dissipation is 0.5 W per input
External wetting - for all input options
Modes of operation:
Dry contact and voltage sense
24 Vdc, 48 Vdc, and 110/125 Vdc
994-0047-5.10-4
iBox/iBox Kit
)
rms
Continued on next page
143