Appendix B: Ibox Kit Default Configurations - GE iBox Installation And Maintenance Manual

Grid solutions
Table of Contents

Advertisement

GE Grid Solutions
Appendix B: iBox Kit Default
Configurations
When shipped as part of an iBox Kit, the iBox COM port default configurations are set to one of the
following:
1
iBox (IBOX-BSC
iBox DNP 3.0 Master Address: 10
iBox DNP 3.0 Slave Address: 1
DNP DPA
Communication Port: COM1
Baud Rate: 9600
Communication Type: RS-232
Modbus Address: 1
Communication Port: COM2
Modbus DPA
Baud Rate: 9600
Communication Type: RS-232
iBox DNP 3.0 Master Address: 10
iBox DNP 3.0 Slave Address: 1
DNP DCA
Communication Port: COM3
Baud Rate: 9600
Communication Type: RS-232
User Name: westronic
WESMAINT
Password: rd
Control Password: control
1
Name of the device within the SGConfig sample project
GE Information
)
Configuration Details
Installation and Maintenance Guide
Comments
Refer to point map tables for more detail.
Refer to point map tables for more detail.
The DNP DCA is configured to poll an iBox. If
you connect COM3 to COM1, you can see the
DNP DCA polling the DNP DPA.
994-0047-5.10-4
iBox/iBox Kit
149