Physical Mounting
Rack Spacing
When mounting the iBox Kit in a rack with other equipment, leave at least one rack
unit (RU) of space above and below the equipment to allow for cooling air flow and
cable routing (1 RU = 1.75 inches or 44.5 mm).
Required
The exterior dimensions of the iBox Kit are:
Clearances
8.75" high x 19" wide x 2" deep (22.2 cm high x 48.3 cm wide x 5.1 cm deep)
Procedure –
To mount the iBox Kit on a rack:
Mounting the
Step
iBox Kit
1
2
3
4
5
Note: iBox Kits should be installed with the equipment modules and LEDs visible
Note: Equipment cabling will typically route along the rack channel, come through
Note: An IEC
You are now ready to connect ground, power, and communications cabling to the
iBox Kit.
GE Information
Determine the location of the iBox Kit in the 19-inch mounting rack.
Insert, but don't tighten the top two mounting screws.
Slide the iBox Kit over the top mounting screws and drop down into position.
Insert the bottom mounting screws.
Tighten all four mounting screws.
from the front of the rack.
a space above or below the iBox Kit then connect to the mounting panel,
iBox, power supply, Ethernet Module and I/O module.
®
60947 compliant main disconnect switch (or other equivalent
device complying with IEC 60947-1 / 60947-3) must be as electrically close
as practicable to the iBox Kit power supply.
Installation and Maintenance Guide
Action
994-0047-5.10-4
iBox/iBox Kit
83