Fail-Safe Electronic Modules
8.2 4 /8 F-DI/4 F-DO DC24V/2A PROFIsafe Digital Electronic Module
8.2.7
Diagnostic Functions of the 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe Electronic
Module
Behavior in Case of Supply Voltage Failure
Failure of sensor supplies Vs1 and Vs2 is indicated by the SF LED, VsF LED, and the LEDs
of the relevant channel group on the F-module. This information is also provided on the
module (diagnostic entry). All channels of the module are passivated.
Diagnostic Functions
The following table presents an overview of the diagnostic functions of the 4/8 F-DI/4 F-DO
DC24V/2A PROFIsafe electronic module. The diagnostic functions are assigned either to
one channel or to the entire module.
Table 8-18
Diagnostic Function*
Short circuit
Overload
Overtemperature
Wire break
Fault
Parameter assignment error
Sensor voltage or load voltage is missing
Communication error
Safety-related shutdown
*: Specifically for F-modules; display in
of Fail-Safe Modules" table
100
Diagnostic Functions of the 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe Electronic Module
Fault
LED
Number
1
SF
H
4
SF
H
5
SF
H
6
SF
H
9
SF
H
10
SF
H
11
SF
H
13
SF
H
19
SF
H
STEP 7
, see the "Channel-Specific Diagnostics, Fault Types
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
Range of
Assignabl
Effectiveness of
e
Diagnostic
Channel
No
Channel
No
Module
No
Channel
Yes
Module
No
Module
No
Module
No
Module
No
Channel
No