D Response Times; Response Times; D.1 Response Times - Siemens SIMATIC Operating Instructions Manual

Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Response Times

D.1 Response Times

Introduction
The response times of the ET 200pro fail-safe modules are presented below. The response
times of the fail-safe modules enter into the calculation of the F-system response time.
For information on calculating the F-system response time, refer to the
SIMATIC S7
Definition of Response Time
The response time is the time between detection of an input signal and a change in the
gated output signal.
The actual response time lies somewhere between a minimum and maximum response time.
The maximum response time must always be anticipated when configuring a system.
For fail-safe digital inputs: The response time is the time between a signal change at the
digital input and safe loading of the -> safety message frame on the backplane bus.
For fail-safe digital outputs: The response time is the time between an incoming safety
message frame from the backplane bus and the signal change at the digital output.
Maximum Response Time of the 8/16 F-DI DC24V PROFIsafe, the Inputs of the
4/8 F-DI/4 F-DO DC24V/2A PROFIsafe, and the F-Switch PROFIsafe
In the case of problem-free operation:
Table D-1
Electronic module
8/16 F-DI
4/8 F-DI/4 F-DO
F-Switch
PROFIsafe
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
system description.
In the Case of Problem-Free Operation
Short-circuit test parameter
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Safety Engineering in
Assigned input delay
0.5 ms
3 ms
10 ms
13 ms
10 ms
18 ms
11 ms
13 ms
11 ms
20 ms
-
14 ms
-
27 ms
D
15 ms
25 ms
56 ms
25 ms
57 ms
-
-
155