Note
Channel-specific diagnostics are always updated as far as the current diagnostic function in
the diagnostic frame. Subsequent, older diagnostic functions are not deleted.
Remedy: Evaluate the valid current length of the diagnostic frame in
RET_VAL parameter of SFC 13.
Possible Fault Types of Fail-Safe Modules
The following table lists the fault types of channel-specific diagnostics. You can obtain
detailed diagnostic information via
Table 5-1
Fault Types of Channel-Specific Diagnostics
Fault type
Diagnostic function in
STEP 7
00001
1
Short circuit
B
D
00100
4
Overload
B
D
00101
5
Overtemperature
B
D
00110
6
Open circuit
B
D
01001
9
Fault
B
D
10000
16
Parameter assignment
B
D
error
10001
17
Sensor voltage or load
B
D
voltage is missing
10011
19
Communication error
B
D
11001
25
Safety-related shutdown
B
D
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
HW Diagnostics
F-module
Special meaning for F-modules
All
Short circuit to L+ on the unconnected sensor wire
Short circuit to L+ sensor supply
Ground short circuit or defective sensor supply
Internal fault in the read circuit/test circuit
4/8 F-DI/4 F-DO
P output driver defective
Short circuit of output to L+ or output driver
M output driver defective
Short circuit of output to M or output driver
F-Switch
Output driver overcurrent
P output driver defective
Short circuit of output to L+ or output driver
Short circuit of output to M or output driver
4/8 F-DI/4 F-DO
Output driver overcurrent
All
-
4/8 F-DI/4 F-DO
Wire break
All
RAM error
EPROM error
Processor failure (expected DIP switch value/actual
DIP switch value)
Internal fault in the read circuit/test circuit
All
Parameter assignment error
All
Module-internal supply voltage
4/8 F-DI/4 F-DO,
Load voltage is defective or not connected
F-Switch
All
Cyclic redundancy check (CRC) error in data
message frame
Monitoring time for data message frame exceeded
All
Discrepancy error
4/8 F-DI/4 F-DO,
Switching frequency too high
F-Switch
5.2 Error Diagnostics
STEP 7
STEP 7
in
.
Diagnostics
using the
37