Connection To Front Connector - Siemens SIWAREX FTA Device Manual

Weighing electronics for automatic scale
Table of Contents

Advertisement

Termination
1L+
1M
Table 4-2
Power supply connection
4.5.4

Connection to front connector

The SIMATIC construction guidelines apply for connecting the 40 pin connector.
Flexible cables with a cross-section of 0.25 to 1.5 mm
insulation from the cable for 6 mm and install wire end sleeves.
4.5.5
Load cell connections
Sensors equipped with strain gauges and that meet the following conditions can be
connected to the SIWAREX FTA:
-
Characteristic value 1.... 4 mV/V
-
Supply voltage of 10.2 V is permitted
The connection is made to the 40 pin front connector. The connection should be
made using the cable described in chapter Accessories.
Termination
Clamp
X1.34
X1.35
X1.36
X1.37
X1.38
X1.39
X1.40
Table 4-3
Load cell connection
SIWAREX FTA
Signal
Remark
24 V DC 1L+
Power supply +
24 V DC 1M
Power supply M
Signal
AGND
SEN+
SEN-
SIG+
SIG-
EXC+
EXC-
Hardware Planning and Assembly
2
can be used. Remove the
Remark
Analog ground (only to be used for
servicing or with an external feed)
Sensor line +
Sensor line -
Measurement line +
Measurement line -
Load cells-Supply voltage +
Load cells-Supply voltage -
4-21

Advertisement

Table of Contents
loading

Table of Contents