ABB 650 series Engineering Manual page 51

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
650 series
Engineering Manual
It is possible to insert more than one IED from the Create New
Object from Template window and the selection window
remains open until the user clicks Close.
Inserting a configured IED in 650 series
Configured IEDs in 650 series in PCM600 are available as *.pcmi files and include
all information that is related to the IED object in PCM600. The configured IEDs
in 650 series is bound to a specific hardware configuration. Configured IEDs in
650 series are available on the Connpack DVD as .pcmi files under the file named
User documentation.
Two alternatives to insert configured IEDs in 650 series:
Use the configured IEDs in 650 series that has been ordered together with the
IED.
Create an own configuration, export the configuration as *.pcmi file and use it
to configure other IEDs.
Procedure to insert a configured IED in 650 series
1.
Right-click the bay and select Import ... to select the IED configuration file
(*.pcmi) , see
Figure
IEC09000644 V1 EN
Figure 29:
Import an IED from the context menu
2.
Import the *.pcmi file from the bay level in the plant structure.
3.
Click OK to insert the new IED object in the plant structure.
4.
Modify the configuration according to the needed application.
5.
Write the configuration to the IED.
29.
IEC09000644-1-en.vsd
Section 4
Setting up a project
45