Station Configuration Description File Types - ABB 650 series Engineering Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
7.1.3
650 series
Engineering Manual
Data-set
LN
LN
LN
LN
LN
LN
IED 1
IEC05000830 V1 EN
Figure 62:
IEC 61850: Horizontal communication principle
Figure 62
shows an example with three IEDs where each one communicates with
all the others.
When a GOOSE message is to be sent is defined by configuring the data set with
the defined trigger option and the GOOSE control block (GoCB). This engineering
process is done in the IET600 station configuration tool. The task involves
configuring lists with the signal, value and quality (data attributes) that belong to
the GOOSE message dataset.
In the opposite direction the standard only defines the IED as a receiver of the
GOOSE message. How the GOOSE input signals are handled must be defined in
the IED application configuration. The SCD file generated by the IET600 station
configuration tool contains these GOOSE data sets as input data. The input data
must be connected to a GOOSE receive function block (GOOSEBINRCV,
GOOSEINTLKRCV, GOOSESPRCV, GOOSEDPRCV, GOOSEINTRCV or
GOOSEMVRCV) in SMT.

Station configuration description file types

The IEC 61850 standard defines SCL-file types in the sequence of engineering.
These files have a different definition, which is explained in IEC 61850–6. Three
of these file types are used in the engineering process for an IED.
ICD = IED Capability Description
The IED name in an exported .icd file is always named
TEMPLATE.
IEC 61850 communication engineering
IEC 61850 Subnetwork
Data-set
LN
LN
LN
LN
IED 2
Section 7
Data-set
LN
LN
LN
LN
LN
IED 3
en05000830.vsd
89

Advertisement

Table of Contents
loading

Table of Contents