Installation and wiring
FR-A820-00770(15K) or higher, FR-A840-00470(18.5K) or higher
Remove the upper screws.
Remove the lower screws.
Pull the jumper toward you to remove.
Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11,
S1/L21).
Power supply
terminal block for
the control circuit
Fig. 2-42:
NOTES
When using separate power supplies, always remove the jumpers across terminals R/L1 and R1/L11
and across S/L2 and S1/L21. The inverter may be damaged if the jumpers are not removed.
The voltage should be the same as that of the main control circuit when the control circuit power
is supplied from other than the input side of the MC.
The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs
according to the inverter capacity.
Inverter
FR-A820-00630(11K) or lower
FR-A840-00380(15K) or lower
FR-A820-00770(15K) or higher
FR-A840-00470(18.5K) or higher
If the main circuit power is switched OFF (for 0.1 s or more) then ON again, the inverter is reset and
a fault output will not be held.
FR-A800
R1/L11 S1/L21
Power supply terminal
block for the control
circuit
R/L1 S/L2 T/L3
MC
Main power supply
FR-A820-00770(15K) to
01250(22K)
FR-A840-00470(18.5K),
00620(22K)
Detailed view and positions of the terminals
Power supply terminal block
for the control circuit
FR-A820-01540(30K)
FR-A840-00770(30K)
Power supply capacity
60 VA
80 VA
Control circuit
R1/L11
S1/L21
FR-A820-01870(37K) or higher
FR-A840-00930(37K) or higher
I002379E
2 - 59