128 Technical data

Ambient conditions

The unit is to be used in a heated indoor controlled environment.
Installation site altitude
above sea level
Air temperature
Relative humidity
Vibration
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008
Environmental testing
Part 2: Tests -Test Fc:
Vibration (sinusoidal)
Shock
IEC 60068-2-27:2008
EN 60068-2-27:2009
Environmental testing - Part
2-27: Tests - Test Ea and
guidance: Shock
Contamination
Chemical gases
Solid particles
Operation
installed for stationary use
0...2000 m (0...6561.7 ft)
For altitudes over 2000 m,
contact ABB.
Output derated above
1000 m (3281 ft). See
section
Derating
(page
111).
0...+40 °C
(+32...+104 °F), no
condensation allowed.
Output derated in the
range +40...+50 °C
(+104...+122 °F). See
Temperature derating
on
page 111.
Maximum 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
10...57 Hz, max.
0.075 mm amplitude
58...150 Hz 1 g
Tested in ABB multidrive
cabinet (ACS880-x07)
according to:
Max 1 mm (0.04 in.)
(5...13.2 Hz),
max 0.7 g,
(13.2...100 Hz) sinusoidal
Not allowed
IEC/EN 60721-3-3:2002:
Classification of
environmental conditions -
Part 3-3: Classification of
groups of environmental
parameters and their
severities Stationary use
of weather protected
locations
Class 3C2
Class 3S1 with IP20/21,
3S2 with higher IP class
No conductive dust
allowed.
Storage
in the protective package
-
-40...+70 °C
(-40...+158 °F)
Maximum 95%
presence of corrosive gases.
For modules and cabinets
in packages: IEC/EN
60721-3-1:1997
Classification of
environmental conditions -
Part 3: Classification of
groups of environmental
parameters and their
severities - Section 1:
Storage
With packing max.
2
2
100 m/s
(330 ft./s
) 11 ms
IEC 60721-3-1
Class 1C2
Class 1S3 (packing must
support this, otherwise
1S2)
Transportation
in the protective package
-
-40...+70 °C
(-40...+158 °F)
Maximum 95%
For cabinet package:
IEC/EN 60721-3-1:1997
Classification of
environmental conditions -
Part 3: Classification of
groups of environmental
parameters and their
severities - Section 2:
Transportation
With packing max.
2
2
100 m/s
(330 ft./s
) 11 ms
IEC 60721-3-2
Class 2C2