8.3
Common Technical Specifications
Valid safety specifications
Class of protection
Type of protection
Climatic ambient conditions
Operation in equipment with fan
Operation in equipment without fan
(module clearance: 40 mm)
Transportation and storage temperature-
Temperature variation
in operation
transportation and storage
Relative humidity
in operation
transportation and storage
Site altitude
in operation
transportation and storage
Pollutants
S0
2
H
S
2
Mechanical ambient conditions
Vibration in operation
Mechanical requirements
System Manual
C79000-B8576-C199-03
Important for the USA and Canada
The following approvals have been obtained for all the modules
listed in this chapter:
UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard
C 22.2 No. 142, Report LR 63533
VDE 0160
I
IP 20 to IEC 529/DIN 40050
when empty slots are covered by dummy front plates
o
0 to 50
C
o
0 to 55
C
Supply air measured at lower inlet of power supply; for a
cabinet assembly, note that the removable power
dissipation depends on the cabinet design, its ambient
temperature and arrangement of equipment.
o
- 40 to 70
C
10 K/h max.
20 K/h max.
(When delivered under 0
on account of possible condensation)
o
95 % max. at 25
o
95 % max. at 25
- 1000 m to + 1500 m
- 1000 m to + 3500 m
0.5 ppm max. (rel. humidity under 60 %)
0.1 ppm max. (rel. humidity under 60 %)
10 to 58 Hz (const. amplitude 0.15 mm)
58 to 500 Hz (const. acceleration 2 g)
Installation in stationary equipment which is not free
from vibrations; installation on ships and vehicles,
allowing for special installation specifications, but not on
the engine.
Common Technical Specifications
o
C, allow 3 h min. settling time
C, no condensation
C, no condensation
8
8 - 31