Common Technical Specifications - Siemens S5-155U System Manual

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

9.2

Common Technical Specifications

Address range
Supply voltage L+
rated value
ripple V
pp
permissible range (including ripple)
reference potential
Voltage for the isolated enable inputs
(only required when enable jumper is inserted)
Line lengths for
Analog input modules with
rated input range of ± 12 mV
and ± 50 mV
Analog input modules with
rated input range of ± 500 mV/± 1 V/± 5 V/
± 10 V/± 20 mA and Pt 100
Analog output modules
Temperature range
in operation
for storage and transportation
Relative humidity
Site altitude
Dimensions (W x H x D)
Weight
System Manual
C79000-B8576-C109-03
Important for the USA and Canada
The following approvals have been obtained for all the modules
listed in this chapter:
UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E 85972 and E116536 for the
466-7LA11 analog input module
CSA Certification Mark
Canadian Standard Association (CSA) to Standard
C 22.2 No. 142, Report LR 63533C and LR 48323 for
the 466-7LA11 analog input module
128 to 255 (0 to 255)
24 V
3.6 V
20 to 30 V
L- = M
ext
F+ = + 24 V
F- = 0 V
50 m max. for shielded cables laid separately
from power system cables (see Chapter 3)
200 m max., shielded
200 m max., shielded
0 to 55
- 40 to 70
95 % max. at 25
3500 m max. above sea level
20 x 255 x 195 mm
Approx. 0.4 kg
Common Technical Specifications
= 0 V
o
C
o
C
o
C, no condensation
9
9 - 5