Siemens S5-155U System Manual page 75

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

Housing
Power supply unit
Modules and slot
assignments in the
S5-135U/155U CC
Slot No.
3
Module Type
923 coordinator
CPU 922
CPU 928, CPU 928B
CPU 948
CP 5XX, CP 143,
1)
CP 5430, CP 5431
IM 300-5
2)
IM 301-5
IM 300-3, IM 301-3
IM 304, IM 308, IM 308B
1) 3)
IM 307
DI, DQ
AI, AQ 1)
IP 241USW, IP 244,
1)
IP 246, IP 247, IP 252
IP 240, IP 241, IP 242,
IP 242A, IP 242B, IP 243,
1) 4) 5)
IP 281
IP 245
6)
IP 257
IP 260,
IP 261
Load power supply
1)
-951
1) Allow for particular module widths; additional slots to the right may be occupied (see Catalog ST 54.1).
2) In the CC with Order No. 6ES5 135-3UA41, only at Slot 163
3) Observe jumper setting on the IM 307; interrupt transmission is only possible at Slots 107 to 131.
4) Operation at Slots 27, 43, 59, 139, 147 is only possible with severely restricted functions, because no interrupts are wired.
5) IP 243 without D/A or A/D converter can be used at Slots 27, 43, 59, 139 and 147.
6) Allow 1 to 4 slots for the DI/DQ 482 to the right of the IP 257.
System Manual
C79000-B8576-C199-03
The housing consists of bolted sheet-steel sections with ventilation
openings at the top and bottom. The housing contains the bus PCB for
electrical and logical interconnection of the modules. All the slots
have guiderails which accept the modules. Male and female
connectors are thus precisely positioned. There is a locking bar at the
top of the housing to prevent the modules from becoming accidentally
detached. Modules with individual locking are secured in the lower
sectional rail. There is a cable duct for incoming and outgoing cables
at the front of the housing.
The power supply unit with the fans is situated in the lower part of the
central controller frame. Depending on the type of power supply, the
input voltage is either 24 V DC or 230/120 V AC. The AC version can
be adjusted to the required AC voltage with a selector switch.
The following table shows which modules can be inserted at which
slots.
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
Electrical connection
S5-135U/155U Central Controller
Mechanical width
4
4 - 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uSimatic s5

Table of Contents