ABB ACH550 series User Manual page 57

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Group 05
Code
Name
0501
LAST EVENT
0502
E1 TIME 1
0503
E1 TIME 2
0504
EVENT 2
0505
E2 TIME 1
0506
E2 TIME 2
0507
EVENT 3
0508
E3 TIME 1
0509
E3 TIME 2
0510
EVENT 4
0511
E4 TIME 1
0512
E4 TIME 2
Resolution
Range
b0: 1 = Bypass mode
b1: 1 = Safeties In
b2: 1 = Run Enable
b3: 1 = Start
b4: 1 = In Auto Transfer
b5: 1 = Bypass Override
b6: 1 = Fireman's Override
b7: 1 = Drive Fault
b8: 1 = Bypass Fault
b9: 1 = System Started
b10: 1 = System Running
b11:1 = Drive First Start
Completed
b12: not used
b13: not used
b15,b14: 0,0 = Off; 0,1 =
Hand, 1,0 = Auto; 1,1 = not
valid
1, days ago
0 - 65535
2, ago
00:00:00 - 23:59:58
See parameter 501
1, days ago
0 - 65535
2, ago
00:00:00 - 23:59:58
See parameter 501
1, days ago
0 - 65535
2, ago
00:00:00 - 23:59:58
See parameter 501
1, days ago
0 - 65535
2, ago
00:00:00 - 23:59:58
Default
Description
0
Status at last event
0
Time since last event, days
0
Time since last event, hr:min:sec
0
Status of 2nd to last event
0
Time since 2nd last event, days
0
Time since 2nd last event,
hr:min:sec
0
Status of 3rd to last event
0
Time since 3rd last event, days
0
Time since 3rd last event,
hr:min:sec
0
Status of 4th to last event
0
Time since 4th last event, days
0
Time since 4th last event,
hr:min:sec
Parameter Descriptions