ABB ACH550 series User Manual page 60

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

58
Group 16
Code
Name
1608
AUTO XFR
1609
OC
TRANSFR
1610
OV
TRANSFR
1611
UV
TRANSFR
1612
AI TRANSFR
1613
BP DISABLE
1614
BP RUN DLY
1615
SAVE
PARAM
1616
DISP ALRMS
1617
DRIVE TEST
1618
PASS CODE
Parameter Descriptions
Resolution
Range
1
0 = NOT SEL
1 = ENABLE
1
0 = NOT SEL
1 = ENABLE
1
0 = NOT SEL
1 = ENABLE
1
0 = NOT SEL
1 = ENABLE
1
0 = NOT SEL
1 = ENABLE
1
0 = NOT SEL
1 = DISABLE
1 sec
0 - 300 secs
1
0 = DONE
1 = SAVE
1
0 = DISABLE
1 = ENABLE
1
0 = DISABLE
1 = ENABLE
1
0 - 65535
E-Clipse Bypass Configurations for ACH550 Drives
Default
NOT SEL
Enabled allows auto transfer to
(0)
bypass on all drive faults except
the conditional faults which
require an additional enable.
NOT SEL prevents auto transfer
to bypass for all drive faults
including the conditional faults.
NOT SEL
Drive over current causes auto
(0)
transfer. Requires global auto
transfer enable also.
NOT SEL
Drive over voltage causes auto
(0)
transfer. Requires global auto
transfer enable also.
NOT SEL
Drive under voltage causes auto
(0)
transfer. Requires global auto
transfer enable also.
NOT SEL
Drive AI loss causes auto
(0)
transfer. Requires global auto
transfer enable also.
NOT SEL
Disables bypass mode.
(0)
0s
Bypass contactor pick-up delay
when starting bypass or
transferring from Drive mode.
0
Save User Settings (SaveImm +
SavePwrd).
ENABLE
Enables alarms to be displayed:
(1)
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
DISABLE
Enables drive test mode. Drive
(0)
contactor is opened.
0
Enter correct password to here in
order to change value of the PAR
LOCK. Default password value is
"123".
Description